CMTI / Combined modules – Transformer post invertors for photovoltaic power stations/ |
|
CMTI consists of a MV distribution unit for connecting with the electrical distribution net, an electric meters panel, invertor modules with the necessary power to convert the energy coming from the solar batteries, a LV panel with a collecting busbar system, and an appropriate power transformer. • CCTPs are modern products, intended for voltage 0.32 or 0.4/(10)20 kV, as well as for transformers with rated power up to 1600 kVA. • CCTPs are used for connection with the electricity distribution net of photovoltaic power stations. • CCTPs are intended for open air installation, at temperatures between - 30° to + 40° and altitude above sea level below 2000 m. • The structure is made of steel sections, covered outside and inside with Maglite plates that guarantee 4 hours fire resistance. The doors and lattices are made of eloxated aluminium sections and eloxated aluminium sheets and etalbond. • CCTPs are with outside servicing, what allows easy substitution of the installed equipment when necessary. • The whole equipment is jointly earthed. • The CCTP's dimensions depend on the power and type of the employed invertors. • CCTP meets the requirements of standard BDS EN 62271 – 202:2007 and the Regulation on the layout of electric systems and electricity conducting lines.
Engineering characteristics: • Rated power up to 1600 kVA • Rated frequency 50 Hz • MV side rated voltage 10/20 kV • LV side rated voltage 0.32/0.4 kV • Thermal stability current 20/0.4 kV 16 kA/1 s • Dynamic stability current 20/0.4 kV 40 kAmax • Degree of protection IP 33
|